Fluke 174830EUS Three-Phase Power Quality Logger with 24quot 3000 A iFlex current probes, EU...

Power Quality

EGP 781,231.50/Each (ex VAT)
EGP 898,416.23/Each (inc VAT)

Compact and rugged, this three-phase power quality logger is for technicians and engineers who need the flexibility to troubleshoot, quantify energy usage, and analyze power distribution systems. Dependable, this logger allows users to log over 500 different parameters for each averaging period.

Stock No. FLK4920771
Manufacturer Fluke
Part No. 1748/30/EUS
Supplied/Stocked By FLUKE

Please enter quantity.

Fluke 1748/30/EUS Offers

Get fast and easy access to the data you need to make real-time decisions about critical power quality and energy with this three-phase power quality logger.

Troubleshoot, quantify energy usage and perform quality of service surveys easier than ever

Compact and rugged, this three-phase power quality logger is specifically for technicians and engineers who need the flexibility to troubleshoot, quantify energy usage and analyze power distribution systems. Fully compliant with international power quality standards such as IEC 61000-4-30 and capable of simultaneously logging up to 500 parameters while also capturing events, this unit helps uncover intermittent and hard-to-find power quality issues more easily than ever. It comes equipped with an Energy Analyze plus software which quickly assesses the quality of power at the service entrance, substation, or at the load, according to national and international standards like EN 50160 and IEEE 519.

An optimized user interface, flexible current probes, and an intelligent measurement verification function that allows you to digitally verify and correct connections make setup easier than ever and reduce measurement uncertainty. Minimize your time in potentially hazardous environments and reduce the hassle of suiting up in PPE by using a wireless connection (WiFi) to view data directly in the field.

Features

  • Measure all three voltage and current phases plus the neutral current
  • Comprehensive logging
  • Measure with premium accuracy
  • Capture dips, swells and interruptions
  • Measure key power quality parameters
  • Optimized user interface
  • Flexible power supply
  • Rugged and reliable
  • Two external USB ports
  • Ethernet connectivity
  • Compact size
  • Highest safety rating in the industry
  • Optimized measurement accessories
  • Battery life
  • Security

Software Features

  • "In-workshop" or "in-the-field" setup and download through PC application software: simple download using USB memory stick, WiFi download, wired ethernet connection or via USB cable
  • Energy Analyze plus application software: download and analyze every measured detail of energy consumption and power quality state-of-health with automated reporting
  • One touch reporting: create standardized reports according to commonly used standards like EN 50160, IEEE 519, GOST 33073 or export data in PQDIF or NeQual compatible format for use with third party software
  • Advanced analysis: choose any available logged parameter to create a highly customized view of logged measurements for advanced correlation of data

Applications

Logs over 500 different parameters for each averaging period. This allows you to analyze power quality in detail and to correlate intermittent events with detailed waveform data, helping to identify the root cause of disturbances.

Calculates current harmonics limits

When downloading data from this logger, the Energy Analyze Plus software can calculate the limits of current harmonics based on installation parameters to predict the overload of the grid according to a wide range of international standards. This powerful predictive maintenance feature enables current harmonics to be observed before distortion appears in the voltage allowing you to prevent unexpected failures or non-compliance situations and increase system uptime.

Easy to use

Designed with the technician in mind, the four current probes are each connected separately allowing flexibility and simplicity. The instrument automatically detects, scales, and powers the probes, so you don't have to worry about ensuring the measurements are correct.

An innovative tangle-free, flat, voltage lead makes connections simple and reliable. The instrument's intelligent ‘Verify Connection' feature, which can be accessed using the PC Setup application automatically checks to make sure the instrument is connected correctly and can digitally correct connections without having to disconnect measurement leads. In the event of a connection error, the power button on the unit will turn from green to amber indicating that the connections should be verified before proceeding.

The logger can also be conveniently and safely powered directly from the measured circuit (up to 500 V). No more searching for power outlets or having to run multiple extension cords to the logging location, which is especially useful when logging at a remote site and when installing inside electrical panels.

Analysis and reporting

Capturing logged data is just one part of the task. Once you have the data, you need to create useful information and reports that can be easily shared and understood by your organization or customers. Fluke Energy Analyze plus software makes that task as simple as possible. With powerful analysis tools and the ability to create customized reports in minutes, you'll be able to communicate your findings and quickly solve problems so you can optimize system reliability and savings. A range of built-in report templates for industry standards such as EN 50160, IEEE 519 and GOST enable one-click reporting so you can create high-quality reports at the touch of a button. Reports can be modified as standards evolve, or new versions become available.

The flexible data views quickly show details of the measurement file in easy to understand formats. The calendar view shown above enables hour/hour, day/day and week/week comparisons simply by selecting the thumbnail views required. Each selected thumbnail is automatically detailed in the lower window.

Advanced data communication and software

  • View real-time measurements wirelessly from outside the panel or from your office using the included Fluke Energy Analyze plus software.
  • Download logged files directly to a USB flash drive that plugs directly into the USB port of the instrument or by wired or WiFi connection to your PC
  • The export function of Energy Analyze plus enables export of one or more logged values with a simple parameter selector

Rugged and reliable

Built to withstand tough working environments, the flexible current probes are IP65 rated and suitable for most installation situations. The optional IP65 voltage adapter ensures safe, reliable operation even in harsh conditions. Standard 6.6' (2 m) leads simplify connection on difficult to access conductors, and optional 16.5' (5 m) leads are useful when installing in difficult locations. With the capability of powering the instruments from the power line up to 500 V, installation is as simple as can be.

Thoughtful design

It includes simple but effective accessories like the MA-C8 adapter making powering the instrument with a line cord easy when not in the field. Ports that aren't always needed in the field are IP65 protected including the Ethernet, USB, AUX and I/O ports protecting for both moisture and dirt ingress. The status LEDs give a quick and clear indication of what the instrument is doing without having to touch any controls. Its compact size means that in most cases it will fit into the available space without any problems.

What's included with the Fluke 1748/30/EUS

  • Logger
  • Neutral Voltage Test Lead
  • 7" (17 cm) Test Lead Set
  • 79" (2 m) Test Lead Set
  • 4 x Current Probes
  • 4 x Black Aligator Clips
  • 2 x Black Aligator Clips
  • Cable Markers
  • Mains Power Cable
  • Mains Power Adapter
  • Cable Marker Kit
  • Magnet Hanger Kit
  • 4 x Magnet Probes
  • USB Cable
  • WiFi/BLE-to-USB Adapter
  • Carrying Case
Specifications
Accuracy
Voltage Range: 1000 VMaximum resolution: 0.1 VIntrinsic accuracy at reference conditions (% of reading +% of range): ±0.1 % of nominal voltage
i17xx-flex 3000IP 24 3000 A Range: 300, 3000 AMaximum resolution: 0.01 A (min. 3.0 A)3, 0.1 AIntrinsic accuracy at reference conditions (% of reading +% of range): ±(1% + 0.03%)
Voltage Range: 42.5 to 69 HzMaximum resolution: 0.01 HzIntrinsic accuracy at reference conditions (% of reading +% of range): ±(0.1%)2
Auxiliary Input Range: ±10 V DCMaximum resolution: 0.1 mVIntrinsic accuracy at reference conditions (% of reading +% of range): ±(0.2% + 0.02%)
Voltage Min/Max Range: 1000 VMaximum resolution: 0.1 VIntrinsic accuracy at reference conditions (% of reading +% of range): ±0.2 % of nominal input voltage
Current Min/Max Range: Defined by accessoryMaximum resolution: Defined by accessoryIntrinsic accuracy at reference conditions (% of reading +% of range): ±(5% + 0.2%)
THD on Voltage Range: 1000%Maximum resolution: 0.10%Intrinsic accuracy at reference conditions (% of reading +% of range): ± 2.5%
THD on Current Range: 1000%Maximum resolution: 0.10%Intrinsic accuracy at reference conditions (% of reading +% of range): ± 2.5%
Voltage Harmonics 2nd to 50th Range: 1000 VMaximum resolution: 0.1 VIntrinsic accuracy at reference conditions (% of reading +% of range): ≥1 V: ±5% of reading, <1 V: ±0.05 V
Current Harmonics 2nd to 50th Range: Defined by accessoryMaximum resolution: Defined by accessoryIntrinsic accuracy at reference conditions (% of reading +% of range): ≥3% of current range: ±5% of reading, <3% of c...
Flicker PLT, PST Range: 0 to 20Maximum resolution: 0.01Intrinsic accuracy at reference conditions (% of reading +% of range): 5%
Electrical Specifications
Voltage Range 100 to 500 V using safety plug input when powering from the measurement circuit100 to 240 V MA-C8 and using standard power cord (IEC 60320 C7)
Power Consumption Maximum 50 VA (max. 15 VA when powered using MA-C8 adapter)
Efficiency ≥68.2% (in accordance with energy efficiency regulations)
Maximum No-Load Consumption <0.3 W only when powered using IEC 60320 input
Mains Power Frequency 50/60 Hz ±15%
Battery Li-ion 3.7 V, 9.25 Wh, customer-replaceable
On-Battery Runtime Typically 4 hours
Charging Time <6 hours
Data Acquisition
Resolution 16-bit synchronous sampling
Sampling Frequency 10.24 kHz at 50/60 Hz, synchronized to mains frequency
Input Signal Frequency 50/60 Hz (42.5 to 69 Hz)
Circuit Types 1-Φ, 1-Φ IT, split phase, 3-Φ delta, 3-Φ wye, 3-Φwye IT, 3-Φ wye balanced, 3-Φ Aron/Blondel (2-element delta), 3-Φ delta open leg, currents only (load studies)
Data Storage Internal flash memory (not user replaceable)
Memory Size Typical 20 logging sessions of 4 weeks with 1-minute intervals and 500 events
Basic Interval
Measured Parameters Voltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental power, DPF, energy
Averaging Interval User selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min
Averaging Time Min/Max Values Voltage, Current: Full cycle RMS updated every half cycle (URMS1/2 according to IEC61000-4-30 Aux, Power: 200ms)
Demand Interval (Energy Meter Mode)
Measured Parameters Energy (Wh, varh, VAh), PF, maximum demand, cost of energy
Interval User selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off
Power Quality Measurements
Measured Parameter Voltage, frequency, unbalance, voltage harmonics, THD V, current, harmonics, THD A, TDD, voltage interharmonics, TID V, current interharmonics, TID A, Flicker, Mains Signaling, under/over deviation
Averaging Interval 10 min for all parameters2 hrs (long term Flicker PLT)150/180 cycles (3 s) for harmonics (requires software license IEEE519/REPORT)
Individual Harmonics 2nd to 50th harmonicGrouping according to IEC 61000-4-7 user configurable depending on application: Sub-grouped (harmonics + interharmonics), grouped or harmonic bins only
Interharmonics 1st to the 50th interharmonic
Total Harmonic Distortion Calculated on 50 voltage harmonics
Events Mains signaling, transients (low frequency)
Triggered Recordings RMS profile: Full cycle RMS updated every half cycle of voltage and current up to 11 s (URMS1/2 according to IEC 61000-4-30)Waveform of voltage and current up to 200 ms, 10/12 cyclesMains signaling...
Inrush RMS profile based on ½ cycle RMS steady state triggering
Flicker In accordance with IEC 61000-4-15 and IEEE 1453
Mains Signaling Two user defined frequencies up to 3 kHz
PQ Health Summarizes power quality measurements in one table. Detailed data available for each parameter
EN 50160 Compliance with standard
Programmable PQ Limits Enables user defined limits for local standards compliance
Standards Compliance
Harmonics IEC 61000-4-7: Class 1IEEE 519 (short time and very short time harmonics)
Power Quality IEC 61000-4-30 Class A, IEC 62586-1, IEC 62586-2 (PQI-A-PI device)
Power IEEE 1459
Power Quality Compliance EN 50160
Safety General: IEC 61010-1: Pollution Degree 2Measurement: IEC 61010-2-033: CAT IV 600 V/CAT III 1000 VPower Supply: Overvoltage Category IV, Pollution Degree 2Li-ion Battery: IEC 62133
Interfaces
USB-A File transfer via USB flash drive, firmware updates, max. supply current: 120 mA
Wi-Fi File transfer and remote control via direct connection or Wi-Fi infrastructure
Bluetooth Read auxiliary measurement data from Fluke Connect® 3000 series modules (requires supported USB to BLE or Wi-Fi/BLE adapter, check for availability)
USB-Mini Data download device to PC
Voltage Inputs
Number of Inputs 4 (3 phases referenced to neutral)
Maximum Input Voltage 1000 Vrms, CF 1.7
Input impedance 10 M&ohm;
Bandwidth 42.5 Hz to 3.5 kHz
Scaling 1:1 and variable
Measurement Category 1000 V CAT III/600 V CAT IV
Current Inputs
Number of Inputs 4 (3 phases and neutral), mode selected automatically for attached sensor
Input Voltage Clamp input: 500/50 mVrms; CF 2.8Rogowski coil input: 150/15 mVrms at 50 Hz, 180/18 mVrms at 60 HzCF 4 all at nominal probe range
Range 1 to 150 A/10 to 1500 A with thin flexible current probe i17XX-flex1500 IP 24
Bandwidth 42.5 Hz to 3.5 kHz
Scaling 1:1 and variable
Auxiliary Inputs
Number of Inputs 2 (Analog with auxiliary adapter, or up to 2 BLE devices simultaneously)
Input Range 0 to ± 10 V DC, or 0 to ± 1000 V DC (with optional adapter), 1 reading/s
Scale Factor Format: mx + b (gain and offset) user configurable
Displayed Units User configurable (7 characters, for example, °C, psi, or m/s)
Wireless Bluetooth Connection
Number of Inputs 2
Supported Modules Fluke Connect® 3000 series
Acquisition 1 reading/s
Environmental Specifications
Operating Temperature -13 to 122°F (-25 to 50°C)
Storage Temperature Without battery: -13 to 140°F (-25 to 60°C)With battery: −4 to 122°F (-20 to 50°C)
Operating Humidity IEC 60721-3-3: 3K6:-13 to 86°F (-25 to 30°C): ≤100%104°F (40°C): 55%122°F (50°C): 35%
Operating Altitude 6561.7' (2000 m) up to 13,123.4' (4000 m) derate to 1000 V CAT II/600 V CAT III/300 V CAT IV
Storage Altitude 39,370.1' (12,000 m)
Enclosure IEC 60529: IP50IEC 60529: IP65 with IP65 rated voltage connector
Vibration IEC 60721-3-3 /3M2
Electromagnetic Compatibility (EMC) EN 61326-1: Industrial CISPR 11: Group 1, Class AIEC 61000-6-5 Power station environmentKorea (KCC): Class A Equipment (industrial broadcasting and communication equipment)USA (FCC): 47 CFR 15 subp...
General Specifications
Tamper Protection Accept securing cables (max. Φ 6mm)
Dimensions 9.1 x 7.1 x 2.1" (23 x 18 x 5.4 cm)
Weight 2.2 lbs (1 kg)
Technical Documents