Fluke 1623-2 GEO Earth Ground Tester

Earth-Ground

EGP 191,177.70/Each (ex VAT)
EGP 219,854.36/Each (inc VAT)

The earth ground testers offer data storage and download capabilities via USB port. They are able tomeasure earth ground loop resistances using only clamps. The tester automatically determines the resistance of the earth ground rod.

Stock No. FLK4325155
Manufacturer Fluke
Part No. 1623-2
Supplied/Stocked By FLUKE

Please enter quantity.

Fluke 1623-2 Offers

The earth ground testers are able to measure earth ground loop resistances using only clamps and are easy to use. For each test, the testers inform you which stakes or clamps need to be connected and the large rotary switch can be used even with a gloved hand.

Features

  • 3- and 4-pole fall of potential, earth resistance loop testing
  • 4-pole soil resistivity testing
  • Selective earth ground rod testing using one clamp
  • Stakeless earth ground rod testing using two clamps
  • IP56 rated for outdoor use
  • USB data storage and transfer

Stakeless testing

With this test method, two clamps are placed around the earth ground rod and each are connected to the tester. No earth ground stakes are used at all. A known, fixed voltage is induced by one clamp and the current is measured using thesecond clamp. Then the tester automatically determines the resistance of the earth ground rod.

This test method only works if a bonded earth ground system exists for the building or structure under test, but most are. If thereis only one path to ground, like at many residential applications, the stakeless method will not provide an acceptable value and the Fall of Potential test method must be used.

With stakeless testing, the earth ground rod does not need to be disconnected-leaving the bonded earth ground system intact during test. Gone are the days of spending time placing and connecting stakes for each earth ground rod on your system - a major time saver. You can also perform earth ground tests in places you've not considered before: inside buildings, power pylons, or anywhere you don'thave access to soil.

What's included with the Fluke 1623-2

  • Fluke Tester
  • Professional Carrying Case
  • Batteries
  • USB Cable
  • Quick Reference Guide
  • Users Manual
Specifications
Temperature Range
Operating Temperature 14 to 122°F (-10 to 50°C)
Storage Temperature -22 to 140°F (-30 to 60°C)
Temperature Coefficient ±0.1% of reading/°C <18°C >28°C
Intrinsic Error Refers to the reference temperature range and is guaranteed for one year
Operating Error Refers to the operating temperature range and is guaranteed for one year
Climatic Class C1 (IEC 654-1), 23 to 115°F (-5 to 45°C), 5 to 95% RH
Protective Type IP56 for case, IP40 for battery door according to EN60529
Safety Protection by double and/or reinforced insulation maximum 50 V to earth. IEC61010-1: 300V CAT II, Pollution degree two
EMC (Emission Immunity) IEC61326-1: Portable
Quality System Developed, designed, and manufactured according to DIN ISO 9001
External Voltage V external, maximum = 24 V (dc, ac <400 Hz), measurement inhibited for higher values
V Ext Rejection >120 dB (16²⁄3, 50, 60, 400 Hz)
Measuring Time Typical six seconds
Maximum Overload 250 V rms (pertains to misuse)
Auxiliary Power 6 x 1.5 V Alkaline (type AA LR6)
Battery Life Span Typical >3000 measurements
RA 3-Pole Ground Resistance Measurement (IEC 1557-5)
Switch Position RA 3-pole
Resolution 0.001 to 10 Ω
Measuring Range 0.020 Ω to 19.99 kΩ
Accuracy ±(2% rdg + 3 d)
Operating Error ±(5% rdg + 3 d)
Measuring Principle: Current/Voltage Measurement
Measuring Voltage Vm = 48 V ac
Short-Circuit Current >50 mA
Measure Frequency 128 Hz
Probe Resistance (RS) Maximum 100 kΩ
Auxiliary Earth Electrode Resistance (RH) Maximum 100 kΩ
Additional Error from RH and RS RH[kΩ]RS[kΩ]/RA[Ω]0.2%
RA 4-Pole Ground Resistance Measurement (IEC 1557-5)
Resolution 0.001 to 10 Ω
Measuring Range 0.020 Ω to 19.99 kΩ
Accuracy ±(2% rdg + 3 d)
Operating Error ±(5% rdg + 3 d)
Measuring Principle: Current/Voltage Measurement
Measuring Voltage Vm = 48 V ac
Short-Circuit Current >50 mA
Measure Frequency 128 Hz
Probe Resistance (RS + RES) Maximum 100 kΩ
Auxiliary Earth Electrode Resistance (RH) Maximum 100 kΩ
Additional Error from RH and RS RH[kΩ]RS[kΩ]/RA[Ω]0.2%
Monitoring of RS and RH with error indicator. Automatic range selection.
RA 3-Pole Selective Ground Resistance Measurement with Current Clamp (RA with Clamp)
Resolution 0.001 to 10 Ω
Measuring Range 0.020 Ω to 19.99 kΩ
Accuracy ±(7% rdg + 3 d)
Operating Error ±(10% rdg + 5 d)
Measuring Principle: Current/Voltage Measurement (with External Current Clamp)
Measuring Voltage Vm = 48 V ac
Short-Circuit Current >50 mA
Measure Frequency 128 Hz
Probe Resistance (RS) Maximum 100 kΩ
Auxiliary Earth Electrode Resistance (RH) Maximum 100 kΩ
Monitoring of RS and RH with error indicator. Automatic range selection. Measurement is not perfo...
RA 4-Pole Selective Ground Resistance Measurement with Current Clamp (RA with Clamp)
Switch Position RA 4-pole with clamp
Resolution 0.001 to 10 Ω
Measuring Range 0.020 Ω to 19.99 kΩ
Accuracy ±(7% rdg + 3 d)
Operating Error ±(10% rdg + 5 d)
Measuring Principle: Current/Voltage Measurement (with External Current Clamp)
Short-Circuit Current >50 mA
Measure Frequency 128 Hz
Probe Resistance (RS) Maximum 100 kΩ
Auxiliary Earth Electrode Resistance (RH) Maximum 100 kΩ
Monitoring of RS and RH with error indicator. Automatic range selection. Measurement is not perfo...
Stakeless Ground Loop Measurement (2 Clamps)
Switch Position RA 4-pole 2 clamps
Resolution 0.001 to 10 Ω
Measuring Range 0.020 Ω to 19.99 kΩ
Accuracy ±(7% rdg + 3 d)
Operating Error ±(10% rdg + 5 d)
Measuring Principle: Stakeless Measurement of Resistance in Closed Loops Using Two Current Transf...
Measuring Voltage Vm = 48 V ac
Measure Frequency 128 Hz
Noise Current (IEXT) Maximum IEXT = 10 A (ac) (RA <20 Ω)
General Specifications
Display 1999 Digit LCD: Display with special symbols, digit height 25 mm, fluorescent backlight
User Interface Instant measurement through TURN and START one button concept. The only operating elements are rotary switch and START button
Robust, Water and Dust Resistant Instrument is designed for tough environmental conditions (rubber protective cover, IP56)
Memory Internal memory storage up to 1500 records accessible via USB port
Dimensions 9.75 x 5.25 x 7.35" (250 x 133 x 187 mm)
Weight 2.43 lbs (1.1 kg) including batteries 16.8 lbs (7.6 kg) included accessories and batteries in carrying case
Technical Documents